Home About Products & Support Buy Now Contact Us Dynagen


ES52 Engine controller

Engine Controller Unit Specifications

back

Operating Voltage
  • 3.5 to 30VDC continuous,pilots outputs via 12Vdc (standard) or 24Vdc (must be specified) plug-in relays.
Operating Temperature
  • -40 to 85º C
Physical Attributes
  • 3.3" wide, 3.3" high, 1.84" deep
  • Weight: 0.65 lbs.
  • Aluminum case, epoxy sealed (black)
Lamps
  • 5 LED's (extra "Timer" LED for ES52") High intensity, regulated brightness
Adjustments
  • Crank disconnect: 12 - 4156 Hz (2 ranges)
  • Overspeed: 44 - 8492 Hz (2 ranges)
  • Crank tries: 1 to 6 times
  • Crank/Rest time: 3 to 35 seconds
  • Single long crank attempt: up to 256 seconds
Speed Sensing
  • Differential input, 8' of twisted pair cable provided with weatherproof CSA/UL certified plug-in connector
  • Input voltage range: 0.1-300Vrms
  • Frequency drift: <1% over entire temperature and voltage range
Protection
  • Reversed polarity:no damage, normal operation when normal polarity restored
  • Annunciator outputs: auto reset fuse
  • Outputs:Main 10amp fuse provided in accessible socket
  • Inputs: electrostatic discharge protection
  • Surge withstand: 4500 W for 0.002 sec.
Outputs
  • All outputs are sourcing i.e. Switched-to-+Vbat when energized
  • Fuel & Starter Outputs:Replaceable relay, outputs rated 5 amp each, continuous
  • 12Vdc relay coils provided standard, 24Vdc coils optional.
  • Annunciator outputs: 300 ma per output
Inputs
  • Failure inputs: low oil, high temp, auxiliary input - switched-to-ground or switched-to-Bat(+); close to fail
  • Lamp test: activates all LED's (sourcing)
Timers
(ES52 only)
  • One malfunction timer output (300 ma sourcing)
  • One of four selectable modes: Glowplug (0 - 32 secs), SmartChoke™, Air Gate (10 secs), or Slow (0 - 256 secs)

back

Standard Terms & Conditions of Sale

Home   |    About Us   |    Products & Support   |    Buy   |    Contact Us